Know the normal state of doors and windows: open, closed, or locked.
Escape fast! (Do not stop to pack.)
Use a different escape route if closed doors feel hot to the touch.
Crawl and hold your breath as much as possible to help reduce smoke
inhalation during your escape.
Meet at a designated outdoor location.
Emphasize that no one should return to the premises if there is a fire.
Notify the fire department from a neighbor’s phone.
Emphasize that no one should enter the premises if they hear sirens in the
house.
If you arrive at the premises and hear sirens, do not enter. Call for emergency
assistance from a neighbors phone.
Smoke and heat detector locations
Selecting a suitable location is critical to the operation of smoke alarms. Figure 5
on page 40 shows some typical floorplans with recommended smoke and heat
detector locations. Use these location guidelines to optimize performance and
reduce the chance of false alarms:
Before mounting alarms, program (learn) them into memory and do a sensor
test from the alarm’s intended location to ensure good RF communication to
the panel.
Locate the alarm in environmentally controlled areas where the temperature
range is between 40 and 100°F (5 and 38°C) and the humidity is between 0
and 90% noncondensing.
Locate alarms away from ventilation sources that can prevent smoke from
reaching the alarm.
Locate ceiling mounted alarms in the center of the room or hallway, at least 4
in. (10 cm) away from any walls or partitions.
Locate wall mounted alarms so the top of the alarm is 4 to 12 in. (10 to 31
cm) below the ceiling.
In rooms with sloped, peaked, or gabled ceilings, locate alarms 3 ft. (0.9 m)
down or away from the highest point of the ceiling.
When mounting to suspended ceiling tile, the tile must be secured with the
appropriate fasteners to prevent tile removal.
Note: Do not mount the alarm to the metal runners of suspended ceiling
grids. The metal runners can draw the magnets field away from the alarm’s
reed switch and cause a false tamper alarm.