NetworX Series NX-8 CONTROL PANEL Installation and Startup
NX-8 Control 10 CHANGING USER CODES: 1) Enter []-[5]-[master code] - The "Ready" LED will flash. 2) Enter the 2 digit user number (alway
NX-8 Control 11PROGRAMMING THE NX-8 CONTROL PANEL ENTERING THE PROGRAM MODE: To enter the Program Mode, press []-[8]. At this time, the five functi
NX-8 Control 12 PROGRAMMING EXAMPLE – Figure 1 (Numerical Data) Zone 1 LED = 1 Zone 4 LED = 8 } Data = 9 To change data in a segment, enter the data
NX-8 Control 13FEATURE SELECTION DATA: Feature selection data will display the current condition (on or off) of eight features associated with the pro
NX-8 Control 14 Segment 2- Phone #1 Backup Control: Programming a "0" in Segment 2 of this location will cause the NX-8 to make the designat
NX-8 Control 15Segment 2: 1 = Zone and Box Tamper and Tamper Restore. 2 = Auxiliary Power Overcurrent, Ground Fault, and Restore for both. 3 = Wirel
NX-8 Control 16 REPORTING EVENTS TO PHONE NUMBER 2 Phone #2 can be used to back up Phone #1 or for a second receiver to multi-report or split report
NX-8 Control 17LOCATION 15 - DIAL ATTEMPTS/BACKUP CONTROL FOR PHONE #3 (2 segments, numerical data) Segment 1, Dial Attempts: Segment 1 of Location 1
NX-8 Control 18 LOCATION 18 - CUSTOM COMMUNICATOR FORMAT (See locations 2, 8, &14) Segment 1: 1 = On for 1800hz transmit; Off for 1900hz. 2= On
NX-8 Control 19 LOCATION 23 - PARTITION 1, FEATURE AND REPORT SELECTIONS (3 segments, feature selection data) Location 23 is used to enable cert
NX-8 Control 2 © 2011 UTC Fire & Security. All rights reserved. These instructions do not purport to cover all details or variations in equipment
NX-8 Control 20 DEFAULT ZONE TYPES (Configurations) Zones can be programmed to be one of twenty different zone types (configurations). Zone types # 1
NX-8 Control 21NOTE: To “null” a zone, program the zone in “Partition Select” as zero (0) in all partitions and do not use end-of-line resistors.
NX-8 Control 22 LOCATION 31 - ZONES 25-32 ZONE TYPE GROUP (8 segments, numerical data) Location 31 contains the Zone Type for zones 25-32. Segme
NX-8 Control 23 LOCATION 37 - SIREN AND SYSTEM SUPERVISION (5 segments, feature selection data) Location 37 is used to enable various system feat
NX-8 Control 24 LOCATION 40 - SYSTEM TIMERS (10 segments, numerical data) Location 40 contains the duration of various system timing functions.
NX-8 Control 25 LOCATION 44 - DURESS CODE (6 segments, numerical data) Location 44 contains the "Duress" code. This Location contains
NX-8 Control 26 AUXILIARY OUTPUT EVENT SELECTION Table 1 DATA EVENT DATA EVENT 0 Burglary Alarm 26 Fire Trouble 1 Fire Ala
NX-8 Control 27 LOCATION 51 - AUTOTEST CONTROL (4 segments, numerical data) Segment 1: Program a "1" if the interval is to be in hours
NX-8 Control 28 LOCATIONS 56- 83 ARE ONLY USED WHEN REPORTING EVENTS TO A PAGER OR USING A SLOW FORMAT SUCH AS 4+2. WHEN USING CONTACT ID OR SIA, THE
NX-8 Control 29LOCATION 59 - TROUBLE COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY (8 segments, numerical data ) Location 59 contains the event code for
NX-8 Control 3Table of Contents 2GENERAL DESCRIPTION ...
NX-8 Control 30 LOCATION 65 - KEYPAD PANIC COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY (2 segments, numerical data) Location 65 contains the tens and o
NX-8 Control 31LOCATION 74 - EXPANDER TROUBLE AND EXPANDER TROUBLE RESTORE COMMUNICATOR CODES, SLOW SPEED FORMATS ONLY (4 segments, numerical data)
NX-8 Control 32 LOCATION 81 - START PROGRAM AND END PROGRAM COMMUNICATOR CODES, SLOW SPEED FORMATS ONLY (4 segments, numerical data) Location 81 co
NX-8 Control 33LOCATION 93 - PARTITION 3 FEATURE AND REPORTING SELECTIONS (3 segments, feature selection data) Location 93 is used to enable certain
NX-8 Control 34 LOCATION 101 - ACCOUNT CODE FOR PARTITION 6 (6 segments, numerical data) The account code sent when partition 6 is reported is progra
NX-8 Control 35LOCATION 109 - PARTITION 8 ENTRY EXIT TIMERS (4 segments, numerical data) Location 109 is used to enter in seconds the Entry and Exi
NX-8 Control 36 LOCATION 115 - ZONE TYPE 3 CHARACTERISTIC SELECT (3 segments, feature selection data) Use "Zone Type Characteristic Selections&q
NX-8 Control 37LOCATION 129 - ZONE TYPE 10 CHARACTERISTIC SELECT (3 segments, feature selection data) Use "Zone Type Characteristic Selections&qu
NX-8 Control 38 LOCATION 142 - ZONE TYPE 17 ALARM EVENT CODE (1 segment, numerical data) Location 142 contains the event code sent for a Contact ID o
NX-8 Control 39NX-8 PROGRAMMING WORKSHEETS (Factory defaults for segments are in bold italics text and "Quick Start" locations are identifi
NX-8 Control 4 GENERAL DESCRIPTION The NetworX NX-8 represents a new approach to security systems design. Drawing on our experience in the world mar
NX-8 Control 40 1 2 3 4 5 6 7 8 Partition #1 Partition #2 Partition #3 Partition #4 Partition #5 Partition #6 Partition #7 Partition #8 LOC PG DES
NX-8 Control 411 2 3 4 5 6 7 8 Enables two call answering machine defeat Enables tone sniff answering machine defeat Requires callback before download
NX-8 Control 42 LOC PG DESCRIPTION DEFAULT PROGRAMMING DATA 23 19 PARTITION #1, FEATURE SELECTION Segment #1 Segment #2 Segment #3
NX-8 Control 43 LOC PG DESCRIPTION DEFAULT PROGRAMMING DATA ZONES 25-32, PARTITION SELECTION (Segment 1=Zone 25 thru Segment 8=Zone 32) Segm
NX-8 Control 44 LOC PG DESCRIPTION DEFAULT DATA 37 23 Segment #3 (Circle numbers to program) 1 2 3 4 5 6 7 8 Box Tamper report enab
NX-8 Control 45 LOC PG DESCRIPTION DEFAULT DATA SPECIAL FEATURES Segment #1 (Circle numbers to program) 41 24 1 2 3 4 5 6 7 8 Enables s
NX-8 Control 46 LOC PG DESCRIPTION DEFAULT DATA AUXILIARY OUTPUT #1, EVENT & TIME Segment #1: Program the event number for output #1 her
NX-8 Control 47LOC PG DESCRIPTION DEFAULT DATA RESTORE COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY Segment #1: Partition #1 Restore code
NX-8 Control 48 LOC PG DESCRIPTION DEFAULT DATA SENSOR MISSING COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY Segment #1: Partition #1 Sensor
NX-8 Control 49LOC PG DESCRIPTION DEFAULT DATA 84-87 32 RESERVED 0-0-0-0 RESERVED 88 32 PARTITION 1, ACCOUNT CODE 10-10-10-10-10-10 _
NX-8 Control 5FEATURE DEFINITIONS Abort - If enabled, the NX-8 will wait the programmed number of seconds in location 40 prior to sending an alarm.
NX-8 Control 50 LOC PG DESCRIPTION DEFAULT DATA PARTITION 5, FEATURE AND REPORTING SELECTION Segment #1 Segment #2 Segment #3 99 33 1 2
NX-8 Control 51LOC PG DESCRIPTION DEFAULT DATA PARTITION 8, FEATURE AND REPORTING SELECTION Segment #1 Segment #2 Segment #3 108 34 1
NX-8 Control 52 126 36 ZONE TYPE 9 ALARM EVENT CODE 7 _ 127 36 ZONE TYPE 9 CHARACTERISTIC SELECT 6-1245-5678 128 36 ZONE TYPE 10 ALAR
NX-8 Control 53APPENDIX 1 REPORTING FIXED CODES IN CONTACT ID AND SIA The table below list the event codes sent for the following reports (if enabled
NX-8 Control 54 APPENDIX 2 REPORTING ZONE CODES IN SIA OR CONTACT ID The NX-8 has the ability to report SIA level 1 transmissions to either or both
NX-8 Control 55APPENDIX 3 EXPANDER NUMBERS FOR REPORTING EXPANDER TROUBLE The tables below list the device numbers that will be reported for trouble
NX-8 Control 56 NX-8 WIRING DIAGRAM For CE labeled products, please refer to page 58 for specific electrical requirements.
NX-8 Control 57TERMINAL DESCRIPTION TERMINAL DESCRIPTION R1 House Telephone Ring (Grey). R Telephone Ring (Red). T Telephone Tip (Green).
NX-8 Control 58 REGULATORY NOTICES LOCAL TELEPHONE COMPANY INTERFACE INFORMATION Telephone Connection Requirements Except for telephone company prov
NX-8 Control 59UNDERWRITERS LABORATORIES INFORMATION The NetworX NX-8 holds the following listings from Underwriters Laboratories (US and Canadian):
NX-8 Control 6 Communication Formats- The NX-8 can report in multiple formats. It is recommended that you use Contact ID or SIA formats if possible. I
NX-8 Control 60 ANSI / SIA CP-01 REQUIREMENTS IMPORTANT NOTE: UL requirements take priority over SIA requirements. To meet SIA CP-01 requirements –
SPECIFICATIONS OPERATING POWER 16.5 VAC 25, 40, or 50 VA Transformer AUXILIARY POWER w/25 VA Transformer 12 VDC Regulated 500 mA
NX-8 Control 7Keypad Sounder Control- The NX-8 can be programmed to sound the keypad sounder for certain events. (See location 39, page 23) Keypad Ta
NX-8 Control 8 begin a new trip count where the next alarm will set the ‘counter’ to 1. If immediate restore is enabled in location 37, the alarms (a
NX-8 Control 9PROGRAMMING THE LED KEYPADS This section describes how to program the address and partition of each keypad as well as the options that